Itho Daalderop Heat Pump Error Code A1 17
The high-pressure switch is a safety device in the refrigerant circuit: at excessive pressure it switches the compressor off. The trigger is often on the water side, such as air in the system or too little flow; if the code keeps returning, an F-gas certified installer must investigate the refrigerant circuit.
Also shown as: A01 17
Applies to: Itho Daalderop WPU 5G and older WPU types with an MFT thermostat (shown there as A01)
Common causes
- Too little flow on the water side of the condenser, for example due to air in the heating or hot-water system or closed valves
- The heating pump or vessel pump delivers too little flow
- The pressure in the refrigerant circuit itself rises too high, for example due to a fault in the circuit
What to check, in order
- Open all radiator valves and underfloor-heating groups and bleed the heating system; poor flow is the most common trigger.
- Check the water pressure of the heating system and top up to between 1.5 and 2 bar if needed.
- Reset the unit once and see whether the code stays away. If it returns, do not keep resetting and call an installer with F-gas certification: you must not work on the refrigerant circuit yourself.
Clear the code and test
- Fix what the checks above found first — a filter cleaned, a setting corrected, power restored. Clearing the code without fixing the cause only brings it back.
- Make sure the heat pump has power and the controller is set to heating or hot water, as you need it.
- Restart the unit as your manual describes and give it time: a heat pump can take ten to twenty minutes to start a full cycle.
- If the unit runs a full cycle with no code, the fault is cleared. If the code returns, write down the code and what the unit was doing (heating, hot water or defrosting) before calling a technician — it speeds up the diagnosis.
When to call a professional
This code usually points to a faulty part, wiring or the control board on a Itho Daalderop heat pump. Run the checks above to rule out the simple causes, then book a technician — and book one straight away if any of these apply:
- The code comes back after you have run the checks and a test cycle.
- You smell burning, see sparks or scorch marks, or the breaker trips.
- Water is leaking and you cannot stop it.
- The fix needs panels opened beyond what your manual describes, or a part tested with a meter, and you are not set up for that.
When you call, give the brand, the code A1 17, your model number (on a label on the type plate, usually on the side of the unit) and the checks you already ran. It shortens the visit.
Repair or replace?
This fault is in professional territory: the fix usually means a major part or board-level work, and the labour adds up. If your machine is already well into its service life, get the repair quote first, then compare it with the price of a current equivalent model before you decide. Paying a large share of a new machine's price to repair an old one is rarely the better deal; replacing a machine over one cheap fault is wasteful too.
Parts that may be involved
High-pressure switch (pressostat)Heating pumpVessel pump
Parts are model-specific. Find your model number first — usually on a label on the type plate, usually on the side of the unit — and match the part to that number before ordering.
Questions people ask about A1 17
What does A1 17 mean on a Itho Daalderop heat pump?
A1 17 means: The high-pressure switch (pressostat) in the refrigerant circuit has tripped. The high-pressure switch is a safety device in the refrigerant circuit: at excessive pressure it switches the compressor off. The trigger is often on the water side, such as air in the system or too little flow; if the code keeps returning, an F-gas certified installer must investigate the refrigerant circuit.
Can I fix Itho Daalderop A1 17 myself?
Only the preliminary checks. Code A1 17 usually means a part, wiring or the control board has failed, which is a technician job. Run the checks to rule out simple causes before you book.
How do I clear Itho Daalderop A1 17?
Fix what the checks above found first — a filter cleaned, a setting corrected, power restored. Clearing the code without fixing the cause only brings it back. Make sure the heat pump has power and the controller is set to heating or hot water, as you need it. Restart the unit as your manual describes and give it time: a heat pump can take ten to twenty minutes to start a full cycle.